MD-AD125-W Motor charging device; AC/DC 100 – 125V
In addition to manual operation, the closing  spring can be charged automatically by an  electric motor every time the breaker is closed  (ON charging method).
If the closing spring is to be charged automati cally whenever the breaker is opened, then this  can be done through an additional auxiliary  contact (AXb) (OFF charging method). As soon  as charging is completed, a visual display on the  front says ?CHARGED?.
The ?CHARGED? signal is also available via the  413 (TS+) and 414 (TS-) terminals (included in  the standard MD configuration).
There is always the option of manual operation  in an emergency. A closing coil (CC) is required  for closing the breaker by remote control, and a  shunt trip device (SHT) is required for opening  it in this way.
This warrants the prevention of pumping, both  electronically and mechanically. The circuit of  the motor is separate from the ON/OFF circuit  (CC, SHT).